EcoSentinel — Smart Environmental Monitoring & AI Energy-Saving System

License: MIT Python 3.11+ ESP32

A closed-loop edge-computing system for real-time environmental monitoring and AI-assisted energy-saving control. Designed for competition demos and engineering-grade reliability — the system stays stable even when the AI goes down.

Core philosophy: AI is the advisor, not the executor. Rule-based controllers with hysteresis, anti-short-cycle protection, and a self-healing orchestrator ensure safe operation regardless of cloud connectivity.


What It Does

Layer Role
Physical ESP32-S3 collects environmental data (temp, humidity, light, air quality, power) via sensors + INA219 energy metering; relays & actuators close the control loop
Edge (Python) Rule-based control (time-of-use setpoints, deadband, min-run/min-stop), AI advisor (DeepSeek/OpenAI-compatible with candidate pool, circuit breaker, local fallback), self-healing orchestrator (I2C recovery, MCU reset, rate limiting)
Dashboard React web UI + Streamlit dashboard; real-time curves, baseline-vs-saving energy comparison, AI candidate metrics, comfort scores

Quick Start

Prerequisites

  • Python 3.11+
  • Node.js 18+ (for the React frontend)
  • (Optional) ESP32-S3 with sensors for hardware mode

3-command demo (simulation mode — no hardware needed)

# 1. Install Python dependencies (core: API / firmware tooling / tests)
pip install -r requirements.txt
# ...and, only if you want the Streamlit dashboard below (adds streamlit/pandas/matplotlib):
#     pip install -r requirements-dashboard.txt

# 2. Run simulation comparison (baseline vs energy-saving)
python -m energy_system.simulation.compare

# 3. Launch the Streamlit dashboard
streamlit run dashboard.py

With React frontend (recommended)

# Terminal 1: Start the Python API server
python api_server.py --port 8080

# Terminal 2: Start the React frontend
cd app
npm install
npm run dev

Open http://localhost:3000 — the frontend auto-connects to the backend API, and falls back to simulated data if the backend is down.

With hardware (ESP32 + sensors)

# 1. Configure params.yaml with your serial port and settings
# 2. Run the main control loop
python main.py

# 3. Start the dashboard (in a separate terminal)
streamlit run dashboard.py

Project Structure

ecosentinel/
├── main.py                  # Hardware-mode main control loop
├── api_server.py            # FastAPI backend for React frontend
├── dashboard.py             # Streamlit dashboard entry
│
├── energy_system/           # Core Python modules
│   ├── algorithms/          # AI advisor, comfort evaluation, energy savings
│   ├── config/              # YAML config loader, runtime settings
│   ├── core/                # Rule-based controller, thermal model, logging
│   ├── hardware/            # Serial bridge, MQTT client, mock drivers
│   ├── power/               # Energy accounting (Wh/kWh integration)
│   ├── resilience/          # Self-healing orchestrator (stale detection → recovery)
│   ├── simulation/          # Digital twin simulator + data generator
│   └── utils/               # Helpers, env loader, file I/O, process manager
│
├── dashboard/               # Streamlit dashboard modules
│   ├── realtime_view.py     # Real-time sensor curves
│   ├── energy_view.py       # Baseline vs saving energy comparison
│   ├── simulation_view.py   # Digital twin visualization
│   └── ...
│
├── app/                     # React (TypeScript + Tailwind) frontend
│   ├── src/
│   │   ├── components/      # UI components (charts, metric cards, controls)
│   │   ├── pages/           # Dashboard, Realtime, Energy, Simulation, AI pages
│   │   └── services/        # API client
│   └── package.json
│
├── firmware/                 # ESP32-S3 Arduino firmware
│   └── esp32_s3_competition/
│
├── scripts/                  # Utility scripts (DeepSeek test, serial tools)
├── tests/                    # pytest test suite
├── docs/                     # Hardware guide & supplementary docs
├── logs/                     # Runtime logs (gitignored)
├── LICENSE                   # MIT
└── CITATION.cff              # Citation metadata

Key Features

1. Rule-Based Control with Engineering-Grade Stability

  • Time-of-use setpoints — different temperature/lighting targets per time-of-day
  • Hysteresis + deadband — ±0.5°C deadband prevents chattering near setpoints
  • Anti-short-cycle — minimum 15-min run time, minimum 10-min stop time for compressor protection
  • State-aware actuation — commands are only sent when relay state actually changes

2. AI Advisor with Graceful Degradation

  • Suggestion mode (default) — AI proposes actions; the rule controller decides
  • Candidate pool — multiple API configs with exploration/exploitation + EMA scoring
  • Circuit breaker — consecutive failures auto-skip a candidate; half-open probing for recovery
  • Local fallback — when the cloud is unreachable, heuristic strategies take over (ventilation, curtain control based on eCO₂/TVOC/temperature)
  • Compatible with DeepSeek and any OpenAI-compatible API

3. Self-Healing & Resilience

  • Stale data detection — triggers safe mode after configurable timeout
  • Auto-recovery actions — I2C bus recovery, MCU soft reset (with cooldown + rate limiting)
  • Audit trail — every self-healing action is logged to logs/incidents_<label>.jsonl

4. Quantifiable Energy Savings

  • INA219 energy metering — integrates power over time → Wh/kWh
  • Baseline vs Saving comparison — run two labels, dashboard shows savings rate
  • Comfort score — ⚠️ retracted claim: this used to say "proving savings aren't from sacrificing comfort". That is not supported. The unified 0–1 score barely moves (baseline 0.493 → saving 0.491), but that is because its temperature term is clamped to 0 outside the 24–28 °C band in both modes while the humidity term (~0.956) carries the score. Under the IPMVP-native metric — percentage of time inside the comfort band [23, 26] °C — the picture reverses: baseline 41.7 % → saving 20.6 %, i.e. the saving strategy halves the time spent in the comfort band. Both numbers are pinned by tests/unit/test_comfort_band.py. Band source: ISO 7730 (PMV ∈ ±0.5 ⇒ ≈23–26.5 °C) and Sinergym (range_comfort_summer = (23.0, 26.0)), which agree.

⚠️ This model has no thermal inertia (established in the second teammate audit, verified here): τ = C_AIR/(U_WALL·A_WALL) = 25000/1800 ≈ 13.9 s while the step is dt = 300 s, so exp(−dt/τ) = 4.16e-10 — every step lands on that step's steady state and the room's heat storage is effectively absent. Consequences: the time-of-day setpoint schedule (including the 07–09 pre-cooling) cannot store coolth, so any claim that depends on when energy is used is not representable in this model; the savings figure therefore reflects a per-step decision, not a scheduling strategy. The parameters are left unchanged on purpose — co-calibrating them (UA ≥ 600 W/K for the AC to have authority, and C_AIR = τ·UA for a 1–3 h time constant) requires measured data; see docs/hardware-runbook.md and scripts/identify_rc.py. Until then this limitation must be stated wherever the 17.6% is quoted.

Which KPIs this repo reports (and where each口径 comes from)

Benchmarking study: report-benchmarks.md (BOPTEST / Beobench / FlexDRL / rl-testbed). BOPTEST is the only one worth learning from, and three of its decisions are now implemented — each with a gate and a mutation test:

KPI 口径 出处
energy kWh over the run —
comfort band share % of time inside [23, 26] °C IPMVP Core Concepts ("percentage of time in comfort band") + Sinergym range_comfort_summer; teammate audit
comfort violation integral out-of-band amount integrated over time (K·h; humidity %·h; illuminance lx·h), split into three components BOPTEST kpis/kpi_calculator.py:237-287 (slack integral); component split from rl-testbed reward decomposition (:242)
peak power 15-minute window mean, then max (plus the raw single-sample max, reported side by side) BOPTEST kpi_calculator.py:404-406 — a single-sample max at dt=300 s is a solver artefact, not a grid event
area_m2, code_version, short_cycle_blocks reporting only area: BOPTEST normalisation; code_version: Beobench version gate idea; blocks: rl-testbed F2 (countable hard constraints)

Three measured results these KPIs exist to expose (3 days, seed 42 — all reproducible via scripts/control_groups.py and the gates):

  1. "Saving energy" is not an achievement on its own. do_nothing uses 13.05 kWh vs the controller's 199.10 kWh (−93.4 %) — but its mean room temperature is 29.91 °C. Any savings claim must be stated together with the comfort constraint, otherwise "just switch the AC off" beats it.
  2. The saving strategy is worse than doing nothing on the IPMVP metric: band share 20.6 % vs 25.6 %, and its out-of-band integral is 141.88 K·h vs 95.03 K·h for the fixed-setpoint baseline (+49 %). The old 0–1 score hid this (0.493 → 0.491) partly because its humidity component is identical in all three modes (248.44 %·h) — none of them controls humidity, so that term dilutes any temperature signal.
  3. The anti-short-cycle logic works, and its counter explains the above: the fixed-setpoint baseline is blocked 111 times in 3 days, while the saving strategy is blocked 0 times — not because it is efficient, but because it barely actuates (its 26–28 °C setpoints sit far above the achievable ~27.3 °C). Its comfort cost is inaction, not a trade-off it chose.
  • Dual-channel metering (optional) — measure both load consumption + solar input simultaneously

⚠️ Simulation numbers are not field measurements. With the current (uncalibrated, demo-grade) building parameters, the deterministic 3-day simulation reports baseline 199.10 kWh vs saving 164.01 kWh → 17.6% savings (comfort score 49.3% vs 49.1%). Earlier revisions of this repo quoted 29.8% / 82.1%: those came from a numerically diverging thermal model (explicit Euler at dt=300 s, above the 2τ≈27.8 s stability limit) and are retracted. The savings claim still needs real-hardware, alternating baseline/saving runs before it can be compared with literature values.

Two estimators, not one. The 17.6% above is a paired comparison (run baseline 3 days, then saving 3 days). A second, IPMVP-Option-C-style estimator lives in energy_system/simulation/aso_experiment.py: it alternates the strategy inside one continuous run (ASO) and extrapolates a outdoor-temperature regression baseline to the report periods — for 6 days at seed 42 it reports 19.12% ± 4.21 kWh (95%), R²=0.82. The two numbers are different estimators and must not be averaged or mixed; each must be quoted with its own method and caveat (see docs/refactor-baseline.md).

5. Observable Evidence Chain

Every sample written to JSONL includes:

  • Energy: power_w, energy_wh, solar_power_w, solar_energy_wh
  • Comfort: comfort_score + raw sensor fields
  • AI: ai_source, ai_candidate_id, ai_latency_ms, ai_score, ai_cloud_error
  • Safety: safe_mode, safe_reason, resilience.*

Configuration

All runtime parameters live in energy_system/config/params.yaml:

Section Key settings
app use_hardware (true/false), run_label (baseline/saving)
serial port, baudrate, timeout_s
ai enabled, control_mode (suggest/execute), model, api_base, candidate pool
control enable_rule_control, safe_mode_stale_s, actuate_min_interval_s
self_healing enabled, auto_i2c_recover, auto_reset, cooldown settings

API keys are NEVER stored in the YAML config. Inject them via:

  1. Environment variable: DEEPSEEK_API_KEY, OPENAI_API_KEY, or AI_API_KEY
  2. Local .env file (gitignored — see .env.example)

Demo Flow (3–5 minutes, competition-ready)

  1. Run baseline (comfort-first, no energy saving) for 30–60 seconds
  2. Run saving (energy-saving with comfort floor) for 30–60 seconds
  3. Open the dashboard: compare power curves + energy savings rate, verify comfort_score hasn't collapsed
  4. Bonus: shine a flashlight on BH1750 or block the sensor — watch adaptive lighting/curtain strategy change in real time

Running Tests

pytest tests/ -q

Hardware

See docs/hardware-guide.md for the complete hardware guide: BOM (budget vs. competition-grade), wiring diagrams, pin assignments, firmware upload instructions, and serial protocol reference.


Citation

If you use EcoSentinel in your research, please cite:

@software{ecosentinel2026,
  author       = {Yifan Wu},
  title        = {EcoSentinel: Smart Environmental Monitoring \& AI Energy-Saving System},
  year         = 2026,
  version      = {1.0.0},
  url          = {https://github.com/Atlas-did/ecosentinel},
  license      = {MIT},
}

GitHub will also display a "Cite this repository" button thanks to CITATION.cff.


License

MIT — see LICENSE for details.